Introduction to Steam Traps and Drip Legs

A steam trap is an automatic valve that allows condensate, air, and other non-condensable gases (CO2) to be discharged from the steam system while holding or trapping the steam in the system. So, Steam Traps separates out the condensate from the mixture. Let’s first try to understand how this mixture forms:

  • Condensate: Condensate forms whenever steam releases its heat energy for any reason.
  • Air: Air exists in all steam pipes prior to system start-up when the system is cold. Air can enter the system through boiler water make-up systems and vacuum breakers.
  • Non-Condensable gases: Gases other than air such as carbon dioxide exist inside steam systems.

So the main function of Steam Traps is to remove the liquid condensate from the mixture to avoid two-phase flow formation.

What is a Drip Leg in Steam Piping

Drip Legs are vertical piping pockets installed in steam piping to collect condensate. Installing drip legs in proper location serves the purpose of a successful, water hammer free, system start-up.

Purpose of Drip Legs

Drip Legs are installed in steam mains to serve following purposes:

  • Drip Legs are used for removing entrained moisture from the steam transmission and distribution lines to ensure high-quality steam for use in various plant applications, while also preventing damaging and dangerous water hammer.
  • As steam travels at high velocity through piping, moisture forms as the result of piping heat losses and/or improper boiler control resulting in condensate carryover.
  • Drip legs are therefore located at points where condensate may accumulate to allow for drainage by gravity down to a steam trap for proper discharge from the system. Since condensate drains by gravity, drip legs must be located on the bottom of piping and designed with diameters large enough to promote the collection.

Drip Leg Installation guidelines

  • Drip legs should be located at Vertical Lifts or Drops, end of the line.
  • In the straight run of piping every 30 to 50 meters.
  • Installed directly ahead of the regulating or control valve, Manual Valves Closed for a Long Time.
  • Provide proper supports (no sagging)
  • Provide slope towards Drip legs.

Drip Leg Categories

  • DRIP Applications: drip traps
  • PROCESS Applications: process traps
  • TRACING Applications: tracer traps. Steam tracing refers to using steam to indirectly elevate the temperature of a product using jacketed pipes or tubing filled with steam

Drip Leg Configuration

Because condensate drainage from steam systems is dependent upon gravity, drip leg (Fig. 1) diameter is critical for optimum removal – larger is better.

Figure of a properly configured drip leg.
Fig. 1: Figure of a properly configured drip leg.

Types of Steam Traps / Steam Trap Types

Steam Traps are classified into three main groups as shown below.

  • Thermodynamic Steam Traps
  • Mechanical Steam Traps and
  • Thermostatic Steam Traps

Fig. 2 clearly explains the types of steam traps.

Different types of steam traps
Fig. 2: Different types of steam traps

Thermodynamic Disc Steam Traps

Thermodynamic steam traps sense the velocity difference of entering fluids. When condensate enters the trap body, it moves slowly relative to the steam and is freely discharged. When flash or live steam moves across the underside of the disc, its velocity is much higher than water, and the high speed creates a pressure drop which closes the valve head. The valve stays shut until the control chamber steam pressure above the valve head drops, thereby allowing the valve to open.

Types: Thermodynamic Disc and Thermodynamic Piston.

Since air moves much faster than condensate; thermodynamic disc traps tend to close in the presence of air and are generally not suited for venting large amounts of air.

Thermodynamic Disc & Thermostatic steam traps: To handle air, a combination of thermodynamic disc traps and thermostatic air vent can be used.

Operation of Disc Trap

  • Disc traps operate as a function of velocity. Under normal operating conditions, condensate and air enter the trap and pass through an inlet orifice, a control chamber, an insulating chamber (to isolate the trap against the effects of the environment).
  • Rated to operate 10 to 600 psig.
  • Small and lightweight therefore easy to install.
  • Frequently inspection required, not energy efficient because of short service life.
  • Not suitable when backpressure is high.
Thermodynamic DISC TRAPS
Fig. 3: Thermodynamic Disc Traps

Thermostatic Steam Traps

Thermostatic steam traps sense the temperature difference of entering fluids. The closure occurs when the fluid, typically hot condensate, has a temperature greater than or equal to a certain threshold value. The hot temperature causes a thermostatic element to move in such a manner that closes a valve. This temperature threshold value is below that of saturated steam.

  • Since air has a temperature significantly lower than steam, thermostatic traps are generally very good at venting large amounts of air. Thermostatic traps are rated to operate from 0 to 300 psig.
  • Fabricated with SS, CS, and cast iron housings.
  • Not effective when dirt and scale are present

Basic types: Expansion, Balanced Pressure, and Bi-Metal.

Expansion Type steam traps:

  • Expansion steam trap elements have an internal filling that expands and contracts with temperature change to actuate the valve, but the filling does not vaporize.
  • Wax elements are in a congealed state when cool, and expand when heated.
  • Petroleum-based elements are in a contracted liquid state when cool, and expand when heated

Balanced Pressure type steam traps:

Balanced Pressure steam trap elements have a filling which is a mixture of water and mineral spirits that generally vaporizes or condenses at near-to-steam temperature to actuate the valve.

Bi-Metal Steam Trap:

Bi-Metal steam trap elements are composed of two dissimilar metal strips bonded together so that temperature change causes a deflection in one direction or its opposite to actuate the valve.

Bellows balanced pressure type (Fig. 4) steam traps are suitable for High capacity whereas Wafer/Diaphragm balanced pressure are suitable for Low capacity. On the other hand Bi-metallic steam traps can be used both for High or low capacity.

Bellows Balanced pressure type steam trap
Fig. 4: Bellows Balanced pressure type steam trap

Mechanical Type Steam Trap

Mechanical steam traps are designed to open for more-dense fluids and close for less-dense fluids. There are two basic categories of mechanical steam traps that operate on the density principle:

  • Float type and
  • Bucket type

Within these categories, there are two types each of density traps: Lever Float, Free Float, Inverted Bucket, and Open Bucket.

Air is less dense than water. Hence, density steam traps tend to close in the presence of air and are generally not suited for venting large amounts of air. For this reason, density traps may contain a separate thermostatic air vent mechanism to handle significant amounts of air.

  • Float & Thermostatic,
  • Bucket & Thermostatic.

Float and Thermostatic Steam Traps

  • Float & Thermostatic steam traps combine the action of two principles: thermostatic and density. Each trap has its own discharge orifice. A valve with a ball float actuator drains condensate when the liquid reaches a predetermined level in the trap. When the flow of condensate diminishes’ the float drops, partially closing the valve to accommodate the flow rate.
  • At the top of the trap is a thermostatic element that opens to discharge all air and non-condensable gases as soon as they cause a small temperature drop within the trap.
  • Operate in between 0 to 250 psig pressure,
  • The condensate valve is located at the bottom and subject to plugging when dirt and scale are present.
  • If the dirt particles prevent the valve from closing, steam energy will be wasted until the condition is detected and corrected.

Inverted Bucket Steam Traps

Inverted bucket steam traps (Fig. 5) use an inverted bucket that is normally submerged and floats only when steam is present. The bucket sinks when the volume of condensate exceeds a predetermined liquid level. When the bucket sinks, the valve at the top opens.

Inverted Bucket Type Steam Trap
Fig. 5: Inverted Bucket Type Steam Trap

Steam Trap Selection Guidelines

Selection of steam traps shall be in accordance with the following:

  • Steam traps in low-pressure steam drip service shall be inverted bucket style, mechanical traps, or bimetallic thermostatic style traps.
  • Steam traps in medium pressure steam drip service shall preferably be inverted bucket-style mechanical traps; alternatively, disc type thermodynamic traps may be used.
  • Steam traps in high-pressure steam drip service shall preferably be inverted bucket-style mechanical traps.
  • Steam traps provided for steam turbine inlet drip service shall be a thermodynamic piston-type trap.

A commonly accepted practice is to use float & thermostatic (F&T) steam traps for low-pressure steam systems up to 30 PSIG, and thermodynamic steam traps for steam pressures over 30 PSIG.

International Codes and Standards for Steam Traps

  • ISO 6552: 1980/ (BS 6023: 1981): Glossary of technical terms for automatic steam traps.
  • ISO 6553: 1980/CEN 26553: 1991 (Replaces BS 6024: 1981) Marking of automatic steam traps.
  • ISO 6554 1980/CEN 26554: 1991 (Replaces BS 6026: 1981) Face-to-face dimensions for a flanged automatic steam trap.
  • ISO 6704: 1982/CEN 26704: 1991 (Replaces BS 6022: 1983) Classification of automatic steam traps
  • ISO 6948:1981/ CEN 26948: 1991 (Replaces BS 6025: 1982) Production and performance characteristic tests for automatic steam traps.
  • ISO 7841: 1988/CEN 27841: 1991 (Replaces BS 6027: 1990) Methods for determination of steam loss of automatic steam traps.
  • ISO 7842: 1988/CEN 27842: 1991 (Replaces BS 6028: 1990) Methods for determination of discharge capacity of automatic steam traps.

Causes of Steam Trap failure

Common Causes of failure of steam traps are:

  • Corrosion, due to the condition of the condensate. This can be countered by using particular materials of construction, good feed-water conditioning.
  • Water hammer, often due to a lift after the steam trap, traps.
  • Dirt, accumulating from a system where water treatment compound is carried over from the boiler, or where pipe debris is allowed to interfere with trap operation.

Steam Traps Performance Assessment

Performance of Steam Traps are assessed using any of the three methods mentioned below:

  • Visual Method-Visual inspection is performed using sight glasses.
  • Sound Method-Involves Distinguishing between Sound Frequencies using auditory equipment.
  • Temperature Methods-Works on temperature difference principle. However, Least Reliable method and hence normally not used

Feature Requirements in Steam Traps

Ideal steam traps should possess the following features for their best performance:

  • The steam trap should allow the condensate to pass and trap the steam.
  • Steam traps must be energy efficient and have negligible steam consumption. The steam trap must ensure that the steam space must be filled with clean dry steam. The type of steam trap will influence this.
  • Steam traps should possess good air venting capability. If air mixes with steam it will reduce the steam temperature.
  • It’s preferable that steam traps should not cause steam flashing.
  • Steam traps must have high Reliability. Sometimes, various external factors can cause unreliability in steam trap usage like
    • Corrosion
    • Water hammer and
    • Dirt or debris accumulation.

Steam trap Installation

Click here to know the steam trap installation best practices.

Print Friendly, PDF & Email

Anup Kumar Dey

I am a Mechanical Engineer turned into a Piping Engineer. Currently, I work in a reputed MNC as a Senior Piping Stress Engineer. I am very much passionate about blogging and always tried to do unique things. This website is my first venture into the world of blogging with the aim of connecting with other piping engineers around the world.

5 thoughts on “Introduction to Steam Traps and Drip Legs

  1. Dear Sir/Madam,
    I am a Piping Designer,
    it’s very nice topic to know all about sta drip leg etc.

    Thanks for good info

    Regards

  2. This is a very good overview on how and when to use different steam trap. Personnaly, for drip leg applications, I prefer the bi-metalic design. I found them more robust and some manufacturer offer an easy feature to adjust the temperature discharge. Remember, drip leg application have very low load of condensate. So if the drip leg is well done, there will be no worries regarding the amount of condensate that accumulate in the pipe.
    Thanks for your excellent post!

  3. Pretty great post. I simply stumbled upon your weblog and wished to say that I’ve truly enjoyed
    surfing around your weblog posts. After all I’ll be subscribing in your feed and I’m hoping
    you write once more soon!

Leave a Reply

Your email address will not be published. Required fields are marked *

Recent Posts

Enable Notifications    OK No thanks