Recent Posts

Nonstandard Valve Model for Pipe Stress Analysis: Angular, 3-way, 4-way, with Actuator

In the process or the power piping industry, many a time several non-standard valves are used for some specific requirements. A few examples of those are Angular Valves, Three-Way valves, Four-way valves, valves with heavy Actuators, etc. This need to be modeled properly to get the actual effect is stress analysis. this article will briefly discuss the modeling of such valves.

Angular Valve With Equal Legs

If the angular valve has equal legs, then it can be modeled using an ordinary valve element. Just put it into a node between two pipes. Pipes can have a different diameter. One half of valve length will be placed through the first pipe direction and one half through another.

Modeling Angular Valve with Equal Legs
Modeling Angular Valve with Equal Legs

Angular Valve With Unequal Legs

If the valve has unequal leg lengths, then it can be modeled using rigid elements. The total weight of rigid elements should be equal to the valve weight. To model temperature expansion the temperature and material should be specified in a rigid element. Also, flanges can be added into end nodes of the valve to check leakage.

 Modeling Angular Valve With Unequal Legs
Modeling Angular Valve With Unequal Legs

Three-Way Valve

The three-way valve can be modeled just using 3 rigid elements. The total weight of rigid elements should be equal to the valve weight.

Modeling Three Way Valve in Start-Prof
Modeling Three Way Valve in Start-Prof

Four-Way Valve

In START-PROF four-way valve can be modeled using 4 rigid elements. The total weight of rigid elements should be equal to the valve weight.

Modeling 4-way Valve in Start-Prof
Modeling 4-way Valve in Start-Prof

Valve with Heavy Wheel, Actuator or Actuator Modeling

In START-PROF the heavy wheel or actuator can be modeled as node weight load at the actuator center of gravity. This mass should be connected to the valve using rigid elements with zero weight to consider eccentricity. Proper modeling of actuator eccentricity is especially important for seismic analysis of piping systems because the eccentric mass will produce a great additional torsion and bending moments on the piping system.

Modeling Valve with Actuator
Modeling Valve with Actuator

Creating Pipe Model in PASS/START-PROF Software

In the context of pipe stress analysis in engineering, a “pipe model” refers to the representation of a piping system used for analysis purposes. Pipe stress analysis is crucial in designing and evaluating piping systems to ensure their safety and reliability under various operating conditions.

The pipe model includes the geometric and material properties of the piping components, such as pipes, fittings, valves, and supports. The goal of pipe stress analysis is to assess the effects of external loads, thermal expansion, and other forces on the piping system to ensure that it can withstand these conditions without failure.

Key aspects of a pipe model in pipe stress analysis include:

  1. Geometry: The layout and dimensions of the piping components, including pipe lengths, diameters, bends, branches, and connections.
  2. Material Properties: The material specifications of the pipes and fittings, including information about the modulus of elasticity, thermal expansion coefficients, and other relevant material properties.
  3. Loads and Forces: External loads, such as pressure, temperature changes, weight, and seismic forces, are considered in the analysis. These loads can lead to stresses and deformations in the piping system.
  4. Boundary Conditions: The support and restraint conditions at pipe supports, hangers, and other connection points are modeled to simulate the actual conditions in the field.
  5. Operating Conditions: The range of temperatures, pressures, and other operating conditions that the piping system may experience during its lifecycle.

Pipe stress analysis is typically performed using specialized software that utilizes finite element analysis (FEA) techniques to simulate the behavior of the piping system under various conditions. The analysis helps identify potential issues such as excessive stresses, displacements, and loads that could lead to failure or damage.

It’s important to note that accurate modeling of the piping system is crucial for obtaining reliable results. Engineers use their expertise along with industry standards and guidelines to create realistic pipe models for stress analysis.

The following training video shows how to create a piping model in Piping Stress Analysis Software PASS/START-PROF

Creating Pipe Model in PASS/START-PROF

Technical Bid Evaluation Criteria and Vendor Offer Review

What is Technical Bid Evaluation(TBE)?

Technical Bid Evaluation or TBE is the organized evaluation and examination process of the vendor’s technical bid documents or proposals from the technical requirement point of view. For all items, a Material Requisition (MR) document is prepared and sent to several vendors stating the requirements for any item on a specific project. Based on availability and experience different Vendors provide their bids or offers. All these offers need to be reviewed before selecting the final vendor. So, Technical Bid Evaluation(TBE) or Vendor Offer Review is an important step before final procurement. This article will provide a sample guide on the general activities to be carried out during Vendor offer review, TBE (Technical Bid Evaluation) & Vendor drawing Review:

The Technical Bid Evaluation basically assesses the technical capability along with the quality, compliance with codes, standards & specifications, experience, operating cost, and performance penalties to meet the project-specific requirement as well as execution capability.

Guide for Vendor Offer Review

The following points are to be checked during the Vendor Offer Review of any item.

  • Offer to be reviewed with respect to Material Requisition.
  • The vendor should be listed in the list of Approved Vendors by the Client.
  • The manufacturer location shall be as per the Approved Vendor List.
  • Scope & Interface clarity is to be checked.
  • Vendor to stamp and comply with MR (Material Requisition), Specification & Table of compliance
  • Technical queries preparation.
  • Check whether the vendor is taking any Deviation with respect to MR.
  • Ensure that the Vendor shall comply with all in-house Specifications, Guidelines, Procedures, Work Instructions, and International Code & Standard requirements.
  • Design Change to be covered as part of TQ (Technical Queries).
  • Response to Vendor TQ clarification.
  • Vendor Clarification Meeting, if required.
  • Close all Technical Queries (TQs) & clarifications.

Guide for Technical Bid Evaluation

While performing technical bid evaluation (TBE), the following points are to be considered.

  • Compile all vendor offers into one document (excel sheet or some other document).
  • List down all the requirements of MR& Specifications.
  • Attach all the Technical Queries, Justification letters, Deviation & Clarification lists.
  • All vendor deviations are to be approved by the Client.
  • Delivery time to be mentioned.
  • Technical Acceptance or Rejection against each vendor is to be mentioned.
  • Issue TBE for Client Comments & Approval
  • TBE (Approved for Purchase) is to be issued to procurement for Commercial Acceptance.
  • After finalization of the Vendor, Purchase Specifications are to be issued to a particular vendor

Guide for Vendor Drawing Review

The following points are to be kept in mind while Reviewing the vendor drawings

  • Vendor drawing to be reviewed with respect to Purchase Specifications.
  • Any design change at this stage will be an additional activity for the Vendor which may incur an additional cost.
  • Drawings are to be reviewed based on technical requirements and to be commented on accordingly.
  • Normally each organization has its own checklists for vendor drawing review and those are to be followed with close attention to avoid any major mistakes.
Technical Bid evaluation of Equipment
Various Types of Equipment for Review

Types of Equipment, Packages & Piping Components that are normally reviewed

Static Equipment for Technical Bid Evaluation

Important static equipment for technical bid evaluation is

Rotating Equipment for TBE

Technical bid evaluation is performed in the following rotary equipment in a process plant

Packages for Technical Bid Evaluation

Important package items used in the oil & gas industry for the technical bid evaluation process are

  • Compressor package
  • Flare package
  • WTP package
  • Separator package
  • Chemical Injection Skids
  • FMS

Mechanical  (Static & Rotating) discipline will be the Lead for Vendor offer review, Technical Bid Evaluation &  Vendor drawing review for Static / Rotating equipment & Packages.

Piping will provide inputs to mechanical.

Technical Bid Evaluation for Piping Components

The main piping items used for technical bid evaluation are

Piping will be the Lead for Vendor offer review, Technical Bid Evaluation &  Vendor drawing review for Manual valves, Relief valves, and Piping Specialty Items.

Technical Bid Evaluation for Valves

The following steps are followed for the TBE of valves.

  • Vendor to comply with MR, mandatory requirements.
  • TQ preparation
  • Review of TQ response from Vendor.
  • TQ-2, if any.
  • Review of vendor deviation, if any.
  • The vendor should comply & stamp on the table of Compliance.
  • Pressure Testing requirements to be checked.
  • Painting requirements are to be marked with respect to line design parameters.
  • For the Full Bore valve requirement, the Valve ID is to be checked.
  • Fire Safe Design requirements are to be checked for soft seated valves.
Sample format for Technical Bid Evaluation, Vendor offer Review
Sample format for Technical Bid Evaluation, Vendor offer Review

Piping Inputs to Vendor Packages for Technical Bid Evaluation

While performing the technical bid evaluation the following inputs are provided from the piping.

  • Vendor to perform the engineering of interconnecting piping between all internal skids of Package.
  • The vendor shall perform the stress analysis/ calculation, and other required engineering for interconnecting piping between all skids of the Package (for example GRC Package-LR Compressor, Air Cooler, Sealing, Drums, etc)
  • The vendor shall provide maximum allowable forces and moments at the interface flanges.
  • Vendor to provide Piping layout drawings, and Isometrics drawings for all Interconnecting piping between all skids of Package.
  • The vendor shall comply with the Client/ In-house Piping Specification & Shell Standard Piping Class
  • Vendor to provide Proper access / Platforms / Ladder for Maintenance and Operation of the GRC Package.
  • Vendor to comply with all client requirements.
  • Vendor to comply with the client Specifications, Guidelines, Procedures, Internal Codes & Standards, and requirements as stated in MR.
  • Location & Available Area for the Packages

Piping Inputs to Static Equipment for Technical Bid Evaluation

TBE of Storage Tanks

  • Nozzle Orientation, Staircase Orientation & Elevations.
  • Allowable Nozzle forces & moments on the tanks’ shell nozzles shall be calculated as per API 650 annex. P
  • Allowable nozzle load on any process nozzles on the roof shall be analyzed using the FEA method
  • Pipe Support Cleat Orientation & elevations.
  • Piping loads at supports taken from Tank Shell / Roof.
  • Platform Access requirements for Rooftop Nozzles
  • Underside elevation of the tank.
  • Tank & piping Interface details

TBE of Heat Exchanger / Air Cooler / Vessels

  • Nozzle forces & moments
  • Piping Interface details
  • Sliding support requirements in case of Tube heat exchanger
  • Nozzle location & elevations.
  • Vendor to comply with the Nozzle Minimum forces & moments as per proper standards
  • Pipe Support Cleat Orientation & elevations.
  • Piping loads at supports taken from Equipment Shell / Roof.
  • Platform Access requirements for top Nozzles

Piping Inputs to Rotating Equipment

Technical Bid Evaluation for Centrifugal Pumps

The following guideline should be satisfied during technical bid evaluation for centrifugal pump selection:

The offered model should be proven and should have been operating satisfactorily for a minimum of 1 year in at least one installation.

The pump should not be selected in case the difference between NPSHA is less than 0.5 meters. NPSH testing must be asked whether the liquid is at/or near its boiling point, the liquid is gas saturated, or wherever NPSHA is less than 3 m.

Pump performance must be corrected for viscous fluids; the performance correction factor given by the vendor should be checked with respect to hydraulic institute standards. An equivalent parameter for water must be mentioned on the datasheet.

In case a low-speed pump is required, a higher-speed pump should not be accepted unless substantiated with plausible technical reasons and operating experience for a similar application.

The pumps required for parallel should have a minimum of 10-20% higher shut-off head than the operating head.

Pump with flat and drooping characteristics towards shut-off should not be selected for parallel operation.

In the case of a single pump operation, the pump minimum flow shall be greater than the flow corresponding to the differential head coinciding with the shut-off head in the drooping characteristics.

In the case of any indigenous pump vendors offering the pump with an inducer, his experience, and technical backup should be checked.

Double volute pumps will be preferred for high-capacity pumps (more than 250 m3/hr) and specifically for applications where continuous part-load operation is envisaged.

Impeller type should conform to that specified in the datasheet, generally open impellers will be preferred for liquid with suspended solids.

Non-standard flanges i,e 1-1/4’’, 2-1/2’’,5’’,7’’, and 9’’ should be provided with companion flanges by the vendor with nuts, bolts, and gaskets.

In the case of large water pumps, suction-specific speed should be calculated at the BEP of the maximum diameter of the impeller. Generally, this should be below 12,000 (US units). Pumps with suction-specific speeds above 12,000 with inducers are only acceptable.

Sundyne pumps with higher specific speeds are acceptable. The vendor should be asked for a reference list for higher specific suction speed pumps. In case the vendor has provided pumps with satisfactory results even with suction specific speed >12000, pumps should be accepted with at least 20% minimum continuous flow of BEP flow.

Flushing piping generally is in SS and in the vendor’s scope of supply. Flushing piping of size less than ½’’ shall not be accepted. Piping with a screwed and threaded connection is not accepted. All the flushing plan piping shall be welded and flanged and terminated with ANSI flanges.

Spring, hardware, and secondary elastomeric of the mechanical seal should be compatible with liquid handled.

In the case of Plan 32 dilution of pumped liquid with flushing, the liquid will take place. The rate of dilution should be obtained from the vendor and should be exceeding the limit specified flow if any.

Cooling/heating fluid quantities must be obtained from vendors. In the case of jacketed pumps where casing, bearings housing, and/or stuffing boxes are required to be jacketed, it should be checked whether the vendor has supplied a pump of similar capacity in jacked construction.

Jacket design/test pressure should be specified in the inquiry.

Material of Construction:

  • In the case of pumps with special metallurgy, it must be confirmed by the vendor if he has supplied an equivalent model in similar metallurgy.
  • Any deviation in the material of construction should be brought to notice for acceptance or rejection.
  • Hardness difference of 50 BHN should be maintained between wear rings. In the case of Austenitic steels, hard-faced wear rings should be asked for.

Heavy-duty base plates wherever absolutely necessary should be taken for pumps conforming to API 610 requirements.

Wherever pumps are expected to start on open discharge valve, motor KW selection shall be as per end of curve KW required. Also, GD2 value starting torque and speed-torque characteristics of the pumps should be asked for all motors rating of pumps starting to open discharge.

Inspection and testing, documentation requirements should be checked according to project specification.

The technical recommendations should be clear and without any open points. Reasons for acceptability/non-acceptability should be clearly indicated.

In the case of vertical pumps, the vertical pumps the installation length of pumps to be asked.

Design and engineering for Interconnecting piping between Fluid Coupling, Flushing Plan, Seal Plan, and Cooler.

Piping Interface flange connections shall be as per ASME B16.5. Confirm nozzle allowable loads shall be 2 times the loads as indicated in Table 5 “External nozzle forces and moments” of API 610.

Technical Bid Evaluation for Metering Pump

These pumps are generally used as dosing pumps. The following major points should be checked while evaluating the offer and making a technical recommendation:

The offer should be not be accepted if the model offered is not developed by the vendor and it is not in operation in at least one installation.

The pumps type i.e. plunger or diaphragm (single, double, sandwich) should be checked as per technical specification. For diaphragm pumps, the vendor should include a diaphragm failure detection device in his scope for double diaphragm pumps.

For very low flow applications (<10 lph), electronic type diaphragm pumps are acceptable. In such cases, motor to be included in vendor scope.

The turndown ratio should be checked. Generally, below 10% rundown, the dosing accuracy of pumps will not be as per API specified limits.

Plunger/piston details such as plunger diameter, stroke length, and strokes per minute should be checked. It should be ensured that the rated capacity furnished by the vendor is correct and matches the quoted volumetric efficiency.

For packed plunger pumps, it is recommended to have strokes per minute less than 100, from a wear and tear point of view. Also, the plunger shall be hardened and the average linear speed at the maximum capacity shall not exceed 1.4 m/s.

Variable-capacity adjustment method shall be checked as per technical specification. If a remote operation is required, the details of the servomotor pneumatic positioned and the operating scheme shall be furnished by the vendor. Instruments groups should be consulted for these schemes.

Specific requirements such as cooling, heating shall be checked as per specification.

NPSHA is to be specified in the pump inquiry specification without considering the acceleration head (based on suction line size and length). NPSHR quoted by a vendor should include acceleration head and same is to be checked from relevant data available in the offer.

Gear and gearbox details should be checked. The gearbox service factor must be at least 1.5 for continuous operation. The manufacturer should be furnished the maximum power rating for the gear. Gears shall be reputed make. The gear ratio should be checked with respect to motor speed.

In the case of a diaphragm pump, the compatibility of diaphragm material shall be checked for suitability of process fluid.

Sandwich-type diaphragm-type pumps, if specified are to be checked for vendor’s reference.

Process side safety valve shall be externally mounted and shall have flanged connections (applies mainly for plunger type).

Externally mounted safety valves should be supplied from approved vendors only.

Technical Bid Evaluation for Centrifugal Compressor

Check deviations furnished by vendors (from specified standards) if the deviations are acceptable or not.

Performance curve should be available and should include the following information:

  • Capacity at surge limit
  • Capacity at the choke point
  • Power versus capacity pressure versus curves.

Check that offered model is a developed model and has been working for a minimum of two years.

Check that the compressor manufacturer has guaranteed pressure at the battery limit specified in the specifications

Generally, the surge limit should be below 75% of the specified rated capacity, and the choke point must not be near the operating point. Also, check the surge limit at the minimum supply frequency of the electric motor.

Check the tip speed and Mach number for all the stages. It is preferred to have lower Mach nos. as it gives better efficiency.

Ensure that critical speeds furnished by vendors are a minimum of 30% away from the operating speed. In the case of turbine drive, any critical speed should not be close to the speed trip value of the turbine.

Bearings should be tilting pads. Hydrodynamic thrust bearings should be suitable for thrust in both directions.

Gear’s and couplings should be spacer type. Couplings and gears should be suitable for higher speed (due to an increase in frequency in case of electrical motor drive and up to trip speed for turbine drive) as required in the specification (Minimum service factor 1.4 for motors drive and 1.6 for turbine drives).

The oil system should conform to API 614 requirements, if not specified. It is generally preferred to have the same capacity as Main oil/Aux.oil/Emergency oil pumps. Oil piping downstream of filters should be SS. Oil pumps should preferably be positive displacement screw pumps.

The cooler should be a removable bundle; water through tube design, conforming to ASME Sec VIII, TEMA ‘C’, and with auto drain traps (for air coolers). Coolers tubes should be a minimum of 19″ OD, 18BWG; waterside fouling factor should be as per design basis with water velocity which should be 1.5-1.8 m/s

Heat loads and surface area available for Heat Exchangers should be obtained from vendors. The coolers should be provided with 10% excess area. The quantity of cooling water required should be checked from heat loads given by vendors.

All major rotating parts should be dynamically balanced. Balancing speed and procedure should be obtained from vendors for records and review.

Guaranteed vibrations should be within limits as per API standards.

The entire single-stage compressor should be preferably provided with inlet guide vanes. IGV is effective only at part load operations. The effect of IGV on multistage compressors is very small, hence, to compare power consumption at part loads, capacity vs. power curves should be obtained for compressors with and without guide vanes. The selection of guide vanes for multistage compressors should be based on techno-commercial considerations.

For all process compressors where leakage of a medium cannot be allowed to lead into the atmosphere, positive sealing should be provided by the vendor.

Controls and protection provided by the vendors must be as per requirements specified in datasheets.

During deciding on motor rating following points should be considered,

Highest supply frequency to the electric motor. Ask the vendor to furnish the performance curve at the highest supply frequency.

Power consumption at the lowest inlet temperature.

Power consumption at worst gas compression (in case of varying composition of gas constituents).

Technical Bid Evaluation for Flare System

A flare system package normally comprises of flare stack with flare tip and molecular seal, water seal drum, and knock-out drum. The following point needs to be checked for preparing a technical recommendation.

Plants may have a normal (corresponding to continuous venting) and a peak load (corresponding to emergency venting) for flares. These may be with wide variations as regards to the capacity. In such cases possibility of using different flare tips for these two loads should be considered also.

Calculations should be obtained from the vendor for the height of the stack. Along with heat radiation, the ground-level concentration of toxic gaseous effluents needs to be considered for this calculation. These calculations should be checked against both Vol. I Ch 13/API RP-521.

Between the flare tips and the molecular seal, there are 2-3 temperature zones. The design temperatures of the material and therefore the material changes accordingly. The length of zones should be obtained from the vendor.

It should be checked no refractory material is used for the flare tip.

If the vendor is supplying material for the flare tip that is different from the one specified, the design temperature for the material should be obtained from the vendor and compared with the required value.

Molecular seal or velocity seal designs should be checked carefully.

It is recommended to include the supporting structure in the vendor scope.

The ignition panel should be forced draft type (using plant air) with electric spark ignition. The natural draft should not be accepted. The air/Fuel ratio for a pilot burner for alternate fuels should be asked from the vendor.

Smokeless capacity is normally specified for the greater of the following loads:

  • Normal load
  • 10% of maximum load.

However, check project-specific also.

Water seal height should be checked for minimum back pressure in the flare header to avoid the seal from breaking (API RP-521).

If the knock-out drum is in the vendor’s scope, sizing details of the knock-out drum should be obtained from the vendor. The basis of sizing should be normally be specified in the inquiry. 5-10% consideration in the flare header can be assumed as a basis.

Pressure drop in flare is important for a low-pressure system like atmosphere storage tanks. This should be obtained from the vendor.

Few more resources for you…
Piping Design and Layout
Piping Stress Analysis
Piping Materials
Piping Interface

Further Studies for Technical Bid Evaluation Criteria

A Guide to Plant Clearances and Access Requirements

Providing adequate clearances and access to process equipment, valves, and instruments are of utmost importance for the proper maintenance, operation, and safety of any plant. This present article can be used as a guideline for the preparation of plot plans and equipment layouts for various process plants, offsite, and utilities. This article covers general requirements for on-shore plant layout of process units, equipment, and general facilities, utility plant, and offsite areas. It gives basic considerations for plant clearances and access, equipment elevation, paving, grading, sewers, and other related items.

Plant Clearances and access for the operation and maintenance of proprietary equipment shall be in accordance with the manufacturer’s or equipment vendor’s drawings/operating guidelines or manual.

Considerations during Plant Layout Design

While designing the plant layout, the following guidelines need to be considered.

  • Process units and other facilities shall be integrated within a common plant area only where independent operation and shutdown for planned maintenance of different facilities are not required.
  • Where the process units and other facilities need to be separated from each other from an operations and maintenance point of view, they shall be located at sufficient distances apart from each other with separating spaces or roads. These shall be interconnected by pipe racks/pipe sleepers. It shall be noted that most of the time, these separating distances are governed by statutory / insurance rules.
  • Layout and design shall be based on, and provide access for, maximum use of specific mobile equipment for normal planned maintenance work.
  • Access ways for mobile handling equipment shall be normally 6m wide with 6m overhead clearance. Overhead clearances shall be finalized only after ascertaining the type of mobile equipment proposed to be used in the plant.
  • Where inaccessible to mobile maintenance equipment, facilities such as davits and trolley beams shall be provided. Proper passages shall be planned for the movement of equipment to the workshop for carrying out repairs and for the provision of maintenance space.
  • The plant layouts shall take into account the requirement of turning radii of mobile equipment and tanker lorries etc. Road-turning radii shall be suitable for the movement of proposed mobile equipment and tanker, lorries on the plant roads.
  • It is essential that the layouts meet statutory and insurance requirements as well as other requirements noted therein.
Plant Layout Design
Typical Plant Layout Design

Plant Clearance and Access Consideration for proper Accessibility

Proper Access shall be provided to equipment, valves, and instruments requiring operational control or normal maintenance during plant operation, by operating passages or elevated walkways, platforms, and permanent ladders.

  • Main operating or service levels are defined, as those areas during plant operation requiring plant personnel to be normally or intermittently present for substantial periods of time.
  • Stairways shall be provided as a primary means of access to main operating or service levels in structures, buildings, or furnaces. Cage ladders are not acceptable as the primary means of access.
  • Storage tanks shall also be provided with stairways where tank heights are more than approximate­ly 6 m. It is preferred to provide independent staircases for lined storage tanks.
  • Auxiliary service platforms are defined as those areas which, during plant operation do not require the presence of plant personnel except for short periods of time.
  • Primary access to platforms attached to vessels, auxiliary service platforms in structures, furnaces, and storage tanks for platforms up to approximately 6 m (20 ft) high, shall be by vertical cage ladders.
  • Auxiliary exists from platforms shall be by means of ladders. Such exists shall be required when platforms are longer than 7.5 m and shall be located so that no point on an operating platform is horizontally more than 22.5 m from a primary or auxiliary exit. The dead-end length of a platform shall not be greater than 7.5 m.
  • The vertical rise of any stairway shall not exceed 4.5 m in a single flight at a maximum angle of 40° and shall provide a minimum clear headroom of 2.1 m.
  • The vertical rise of ladders shall not exceed 5 m for a single run. Ladders that are located or extended more than 2.25 m above grade shall be provided with safety cages. Ladders that rise more than 5 m shall have an intermediate rest platform.

For equipment requiring operational control or normal maintenance during plant operation:-

Platforms or ladder access not less than those specified herein shall be furnished for equipment, locat­ed more than 3.6 m above grade and 2.1 m above another platform and include the following means of access:

  1. Where regular access is required, a minimum clear aisle width of 0.75 m and overhead clearance of 2.3 m shall be provided.
  2. Groups of valves at battery limits in elevated pipe racks and grade pipe sleepers shall be provided with permanent platform access. The type of valves (gate, plug, ball, etc.) shall be taken into account when locating such platforms.

Exceptions: Flanged nozzles on vessels, block valves in pipe racks (not requiring operation except for infrequent isolation) metal temperature measuring points in piping, and orifice flanges in lower pipe racks shall NOT be provided with permanent means of access.

Elevated platforms shall have sufficient space as defined herein for maintaining equipment; tall columns shall be provided with davits for removing covers, relief valves, blinds, etc. and the same shall be located such that these can be lowered safely to ground level.

Plant Layout Design Rules for Manual operation of valves

Valves requiring operation during plant operation or in an emergency shall be located as follows, otherwise, such valves shall be equipped with chain operators or extension stems:

  • Horizontally installed valves 6″ (150 mm) and smaller – the bottom of the handwheel shall not be higher than 2.25 m or the maximum height to the centerline of the handwheel shall be 2.3 m above grade or platform, whichever governs.
  • Horizontally installed valves 8″ (200 mm) and larger – maximum height to the centerline of the handwheel shall be 1.95m.
  • The preferred height to the centerline of all valves shall be 1.5 m above grade or platform.
  • Horizontally installed wrench-operated plug, ball, or butterfly valves shall be positioned so that the wrench movement arc is no higher than 2.3 m above the grade or platform.

Equipment Clearance and Access Guidelines

Layout and Safety Design Rules for Furnaces and Fired Heaters

  • Several furnaces in the same or different services and part of the same process unit or facility, together with associated close-coupled equipment, may be located in a single area and shall be segre­gated within that area only as required for operational and maintenance requirements.
  • To avoid a hazard, a furnace and close coupled equipment or a furnace area shall be located not less than 15m and preferably upwind (prevailing) from other equipment containing flammable flu­ids, except as follows :
    • The distance shall be measured from the outside of the nearest of furnace walls to the nearest point of the equipment considered.
    • Not less than 15 m from air coolers, containing flammable fluids.
    • Gas or liquid reforming furnaces, as used in ammonia and similar plants, may be located at a minimum distance from associated process equipment consistent with operating design and maintenance requirements.
  • Reforming and desulphurizing furnaces may be located at a minimum distance from their reac­tors and feed/effluent exchangers, consistent with operating and maintenance requirements.
  • Not less than 15m from switch rooms, un-pressurized control houses, and the compressor or pump house containing equipment in hydrocarbon service. These distance requirements shall generally be governed by statutory / TAC regulations.
  • Furnaces shall be located at a maximum practical distance from process equipment containing liquefied petroleum gas or similar materials in accordance with applicable Tariff Advi­sory Committee (TAC) rules with a minimum distance of 15 m.
  • Integral-type fired heaters such as start-up heaters shall be considered exceptions.
  • Fired furnaces of the following types that are used only for planned intermittent and start-up service may be located at a minimum practical distance from the equipment which they serve and not less than 6 m from other equipment, including air coolers containing flammable fluids.
    • Furnaces having welded coils and no header boxes.
    • Furnaces with header boxes facing away from other equipment.
    • Vertical cylindrical furnaces.
  • Areas for tube pulling shall be as shown on the plot plan and may extend over roads that are periph­eral to the unit and not required for access to other plot areas.
  • Furnaces shall be provided with platforms for operation and access as follows:-
    • Platforms for maintenance of soot blowers and dampers.
    • Platforms for burner operation when inaccessible from grade or in accordance with client requirements.
  • Platforms for access / observation doors except that when the doors are located less than 3.6 m above grade or another platform, access shall be by ladder only.
    • Platforms for header boxes containing removable plug fittings.
    • Platforms for decoking / swing elbow connections.

Plant Clearance and Access Considerations for Heat Exchangers, Air Coolers & Cooling Towers

Shell and tube heat exchangers at grade shall generally not be stacked more than two units high, with a maximum bundle weight of ten tonnes.

Permanent steel or reinforced concrete structures with monorail beams shall be provided for supporting bundles during pulling and lowering to grade if any of the following conditions apply :

  • When specified available mobile equipment is not suitable.
  • Shells stacked more than two units high.

For Shell centreline, more than 3.6 m above grade and Bundle weight exceeds ten tonnes

  • Platforms shall only be supplied where required for operation.
  • Although platforms shall not be provided for access to exchanger’s heads, the layout shall be arranged to facilitate maintenance.
  • Bundle removal of elevated air coolers may be over adjacent equipment where suitable cranes are available, otherwise, crane accessways shall be provided for removing bundles.
  • Access shall be provided for the maintenance of fan drives and headers as appropriate.
  • Proprietary plate type, double pipe, or multiple heat exchangers installed at grade will not be provided with handling or tube pulling facilities.

Air-cooled exchangers may be located at a grade above other equipment or structures, or above overhead pipe racks, subject to the effects of other equipment or structures on air cooler performance and as stated in the below paragraph

Air-cooled exchangers containing flammable fluids shall NOT be installed directly above control rooms, MCC rooms, transformers, and other major switchgear.

Water sprays shall be provided over equipment in the following services located directly beneath air-cooled air exchangers containing flammable fluids.

  1. Pumps handling flammable fluids with an operating temperature above the auto-ignition temperature or 260°C (560°F) whichever is less or,
  2. Pumps handling light hydrocarbons with a vapor pressure greater than 3.5 kg/cm² at 38°C (100°F) or with a discharge pressure in excess of 35 kg/cm² or
  3. Compressors in flammable vapor service.

Equipment adjacent to cooling towers should be located at a sufficient distance downwind as determined by each season’s prevailing winds from cooling towers, to minimize detrimental effects during fog-creating seasons.

The location of cooling towers with respect to roads should be considered carefully as the fog created under certain conditions of temperature and humidity presents a serious driving hazard. If necessary, roads should be provided on both sides of critically located cooling towers; public highways should be located at min. 45 m from cooling towers.

Reactors, Towers, and Vessels: Monorail beams shall be provided for charging reactors only when the use of a crane is not feasible.

Design Rules for Structure Clearance and Access

  1. Ladders shall generally be arranged for the side exit. Step-through ladders may be used for runs from grade up to a height of approximately 6 m or for elevated runs of approximately 3 m.
  2. Where ladders are not provided for access between platforms, intermediate steps shall be provided where the difference in elevation is more than 0.35 m.
  3. Handrailing shall enclose all stairways and platform areas where the clearance between the equipment and the edges of flooring is greater than 0.3 m. Toe plates only shall be provided around floor openings for permanent equipment where the clearance to the edge of the flooring is greater than 50 mm but less than 0.3 m. Handrails shall be provided at the periphery of tank roofs adjacent to access stairways and dip hatches.
  4. Sheds for pumps, compressors, and other equipment, if provided, shall be as follows.
  5. Where compressor sheds (or utility sheds) are provided they shall be open-sided steel frame structures, sheeted from roof eaves level down to a maximum height of 2.45 m above the compressor house floor level, with ventilation by means of natural draught.
  6. Where pump or equipment sheds are provided they shall be steel framed with sheeting as described in (a) above.

Compressor houses shall be provided with suitable facilities for handling the heaviest machine component during normal maintenance including the following (but excluding motor drivers):-

  1. A laydown area and suitable road access for this area shall be provided adjacent to the compressor house.
  2. The compressor house ground floor shall be designed to carry the internal parts of the machines, but not the top halves of casings, during maintenance.

The design of structures containing equipment shall not provide for the removal of equipment, not cons­idered a normal maintenance requirement, except as follows :

  1. To provide access to mobile equipment.
  2. To provide clearance within the structure
  3. To provide for the removal of sections of the structure where specified.
  4. Facilities for breakdown maintenance of vital equipment, the failure of which would seriously affect plant certification and/or production, e.g. Standby Generators / Power units.

Layout rules for Pumps and Compressors

Where permitted by the equipment design, the provision shall be made to allow the removal of the pump internals or driver without dismantling the piping or removing the isolation valves. For this purpose, a flanged spool piece or strainer on the pump nozzle shall be considered satisfactory.

  1. Pump isolation valves shall be located in the pump area as close as feasible to the pump and operable from grade. Valve hand wheels shall be oriented to leave clearance over a pump for maintena­nce and to permit operation without leaning over the pump.
  2. Pump / Compressor isolation valves shall be located near the equipment in such a fashion that no excessive loads are transferred to the Pump / Compressor nozzles.

In general, the drive ends of groups of similar pumps in process and utility plant areas shall line up. In offsite areas, the pump ends of the plinths of groups of pumps shall line up. Large pumps may be orientated parallel to a pipe rack or passage.

The alignment bellows for pumps shall not be mounted directly on pump nozzles. A flanged spool piece of sufficient length shall be installed and anchored between pump nozzles and the bellows.

Clearance and Spacing Rules for Buildings

Where practicable, central control rooms, MCC rooms, and substations shall serve several process units, utility plant, and offsite facility areas. Suitable isolation of utility supply shall be provided where required.

However, where impracticable, or as per the client’s operating philosophy, separate control/MCC rooms may be provided for utility and offsite areas.

Control rooms and switch rooms shall be located as follows:-

  • In an area which shall be at a safe distance from the nearest normal source of flammable hazard (Safe distance as per statutory or TAC rules) or,
  • When not located in a safe area shall be of pressurized design with the top of the air intake stack located in a safe area. In such cases, the construction may have to be blast-proof.

Design rules for Piping

  1. In general, process lines, utility headers, and instrument and electrical cables in process and utility plant areas shall be routed on overhead pipe racks at established elevations and in offsite areas on pipe sleepers at grade level.
  2. In general, lines to equipment in process and utility plant areas will be run overhead of maintenance and operating passages. However, short runs of pump suction and similar lines may be run at grade level where they do not obstruct maintenance access. Where the crossing of general walk­ways is unavoidable, walkover platforms shall be provided.
  3. Offsite pipe racks/sleepers shall normally be located adjacent to storage tank dykes and roads.
  4. Within dyked areas, lines shall be run by the most direct route, as limited by flexibility and tank settlement. Lines at grade serving tanks in a dyked area shall not pass through adjoining dyked areas.

Insulated lines passing through dykes shall be enclosed in sealed sleeves, and uninsulated lines shall be coated and wrapped. Insulated lines under road crossings, and all pressure lines beneath rail­road crossings, shall be enclosed in sleeves unless they are run in culverts.

When located below grade, piping provided with protective heating and piping and services requiring inspection and servicing shall be in built-up trenches.

Cooling, potable, fire service, and similar water piping, shall generally be buried with the centerline of the pipe below the frost line, or be provided with means to prevent freezing.

Buried piping shall be provided with a protective covering of at least 0.3 m.  In cases where heavy load traffic is expected, the minimum coverage may be 1.0 m with/without higher than the normal thickness of piping.

  1. At all changes in direction piping requiring frequent (at least once a week) cleaning shall be provided with flanged fittings or with five diameters (minimum) bends. The run of pipe between flanged cleanout points shall be limited to 12 m for cleaning from one end, and 24 m for cleaning from both ends.
  2. Lines that require occasional cleaning shall be provided with sufficient breakout flanges for disman­tling.
  3. Piping from pressure-relieving devices such as safety valves that discharge to a closed system shall generally be arranged to drain to headers without pocketing of lines and accumulation of condensates at the safety valves.
  4. The flare headers outside process unit areas shall be elevated and self-draining to the flare knockout drum. Flare auxiliaries, such as the ignitor station and steam injection control valve, shall be located near the drum. The line between the flare and the drum shall drain to the drum.
  5. Where practicable piping shall be designed to accommodate expansion without using such devices, such as expansion bellows, cold springing, etc. Line spacing may be based on anticipated line movements under normal operating conditions, if practicable.

Rules regarding Height for Atmospheric Discharge

  1. The top of stacks and continuously operating vents discharging hazardous vapors shall be at least 3 m above any platform or flat building roof, within a horizontal radius of 21 m from the stack or vent. This vertical clearance may be reduced by the same distance that a platform or building roof exceeds 21 m. However, the height shall be governed by State Pollution Control Board regulations and the HAZOP/hazard studies.
  2. The top of the outlet piping from relief valves and intermittent vents discharging hazardous vapors to the atmosphere shall be at least 3 m above any platform of a flat building roof within a radius of 15 m. This vertical clearance may be reduced by the same distance that a platform or roof exceeds is 15 m from the outlet piping.
  3. The discharge of steam, air, or similar non-flammable vapors from relief valves and continuously operating vents, shall be located to prevent any hazard to personnel.
  4. Minor vents, controlled by an operator, may discharge to the atmosphere local to the equipment vented subject to restrictions as noted above.

Guidelines for Flares

The location of flares shall be determined in accordance with client requirements, and vendor recommendations and in reference to the limitations of the ‘Guide for Pressure Relief and Depressurising Systems’ – API – RP.521.

  1. It is desirable that the flare shall be positioned upwind of process units and tankages, to reduce risks of ignition of possible vapor leaks.
  2. The safety zone around the flare stack shall be decided based on an acceptable radiation level at grade. This zone shall be isolated by means of a fence.

Design Rules for Maintenance and Equipment Handling

  1. Handling facilities shall be limited to the handling of working parts of equipment that require frequent or routine service and which are inaccessible to the handling facilities assumed to be available at the plant. Such facilities shall not be designed to handle heavy parts which normally are unaffected, such as the bedplates of rotating machines, rotating equipment, the bodies of compressors, machinery, frames, etc.
  2. Special consideration must be made where major machines are involved (e.g. multi-case compressor trains) where heavy lifts are likely and laydown areas are required. Clear passages to workers are also required in such cases.
  3. The design and installation of monorail beams, overhead traveling cranes, and hoist trestles shall be based on lifting the parts to be handled and transporting them or lowering them to specified maintenance areas or to grade. From these points, they are expected to be removed by skids or hand trucks to other areas which are more suitable for maintenance.

Requirements for Paving, Surfacing, and Grading

Paving shall be provided as shown on the plot plan. Walkways to buildings only and the following areas shall be paved subject to client’s discussions, on a contract-to-contract basis.

  • The areas below bottom oil-fired or combustible liquid-containing furnaces and under elevated structures support coke drums or catalyst-containing vessels.
  • The areas around groups of two or more pumps are located outdoors, extending approximately 1.2 m beyond the pump foundations with bunds on all sides.
  • The areas around process equipment :
    • Drainage facilities shall be provided to recover spilled materials or drain to the chemical/effluent system.
  • The areas around rail and road loading installations, additive and metering facilities, extending approximately 1.2 m around the facility with bund on all sides.
  • Areas below pressurized spheres and bullets.
    • Curbs, when required to retain spilled materials, shall normally extend from the bottom of the paving to a height sufficient to contain the full contents of the largest atmospheric tank in the area. Concrete surfaces normally exposed to acids or similar corrosive materials shall be provided with protective coatings such as acid/alkali-resistant tiling.
  • All paving shall be sloped towards drainage points, the minimum slope shall be 1 in 125 and the maximum fall shall be 150 mm, except for floors of control rooms, operator houses, and MCC room which shall be laid level. High points of paving shall generally be coincident with the finished floor elevation applicable to the area under consideration.
  • The type and surfacing of roads and access ways for maintenance vehicles access shall be as shown on the plot plan.
  • Unpaved areas within the battery limits of utility plant and process unit areas, administration and parking areas, shall be graded and surfaced with a minimum of 50 mm of gravel, crushed stone, or other suitable material.
  • Offsite areas such as tank farms inside bund walls, pipe racks, and areas alongside roads, will not normally be surfaced except where required for maintenance or as specified in statutory regula­tions.
  • Finished grade elevation of different plant areas or within the battery limits of an area, may be varied and established to permit adequate drainage.
  • Roads shall be ramped over piping at the intersection with grade-level pipe sleepers, if possible. If not, suitable culverts shall be provided for the passage of pipes.

Design Considerations for Pipe Trenches and Pits

  • In general, pipe trenches shall have concrete or brick side walls, open tops covered with grating or plate, and bottoms surfaced with crushed stone.
  • Paving with acid-resistant titles shall be furnished in acid or similar corrosive services, and shall be sloped for drainage, with a drainage sump at the lowest point.
  • The following items shall be considered :
    • Firestops shall be provided where trenches cross-unit battery limits, or to maintain separate areas, such as totally enclosed buildings, furnaces, or grouped equipment.
    • Pipe trenches located near fired heaters or any sources of ignition shall be backfilled with sand and be provided with sealed covers.
  • The minimum width of pipe trenches shall be 450 mm. A minimum clearance of 100 mm shall be provided between the outside of the pipe, flange or insulation, and walls, and 50 mm to the high point trenches bottoms.
  • Pipe trenches in paved areas shall be covered with plate or grating set flush with the top of the paving, and in unpaved areas shall be covered with a steel plate set 50 mm above the high point of adjacent grade. Trenches inside buildings shall be covered with MS / CI grating set flush with the floor. Trenches subject to vehicle traffic shall be provided with removable reinforced concrete covers set flush with the surface.
  • Where provided, pits shall have concrete/brick walls. Floor surfacing of pits shall be concrete. Pits shall have a sump for the collection of drainage.  The pit floor shall slope towards the sump.
  • Access to pits shall be by ladders or ladder rungs cast into the walls. Stairways shall be provided for pits containing equipment such as vessels, pumps, and exchangers. Auxiliary exit ladders shall be provided if any point on the pit floor is more than 7.5 m from a main or auxiliary exit.
  • Open pits shall be provided with handrailing and 150 mm high curbs above the grade level.
  • Closed pits shall be provided with suitable removable covers set flush with paving in paved areas or 50 mm above grade in unpaved areas. Sealed covers, with a vent, piped to a safe location shall be provided for pits located near fired furnaces or similar sources of ignition.

Few more resources for you…
Piping Design and Layout
Piping Stress Analysis
Piping Materials
Piping Interface

Further Studies

Major features of CAESAR II-2019, Version 11.00

The upcoming CAESAR II release will deliver a number of significant new and extended capabilities in response to current market requirements, as well as direct feedback from the growing CAESAR II user community. Currently, they are running their beta testing for the new version of the software. From that beta software, We come to know that The following changes will have been made to CAESAR II 2019, Version 11.00

Piping Input:

  • Added the CAESAR II Determines option to Allowable Stress Indicator for the B31.8 code, similar to the existing implementation for B31.4. CAESAR II Determines specifies that the software selects the stress equations based on the calculated axial load in the piping system.
  • Added node name and node number formatting options to Options > Node Numbers. You can now display names and numbers with the same formatting available for Options > Node Name in the Static Output Processor. 
  • Updated and renamed the Global Coordinates and Global commands to View/Set Coordinates. The new Global Coordinates dialog box displays a grid view of nodes and coordinates for all disconnected elements, and you can edit the values.
  • Updated the Coordinates and Elements lists to support the new View/Set Coordinates command. The start (From) node displays in the Node column of the Coordinates list. Right-click > View/Set Coordinates displays on the Coordinates list. Disconnected element rows highlight in green in both lists.
  • Extended the range for node numbers. A node number previously had a maximum value of 32,000. It now has a maximum value of 8,000,000. Refer Fig. 1
  • Improved the efficiency of processing disconnected segments to function with the extended node number range.
  • Improved the behavior of node names. The same node name now displays on all elements sharing the same node.
  • Increased the maximum length of node names from 10 to 25 characters.
  • Increased the number of Uniform Loads from three to nine vectors
  • Added a restraint legend which allows you to visually identify and edit restraint gap values.
  • Added the Rigid Type option to the Rigids auxiliary data tab. When you define a rigid type, the software graphically displays that type for the element in the model view.
  • For the ISO-14692 2005 code, allowed editing of the Pressure SIF box on the SIFs/Tees auxiliary tab. You can now change the value in both boxes from the default value of 1.3. 
  • Adjusted the density for material (191) A335 P91.
  • Added the ability to create multiple toolbar and command profiles. You can switch between profiles as needed. Delivered a new functional profile as the default profile.
First look of Caesar ii 2019 with increased node number option
Fig. 1: First look of Caesar ii 2019 with increased node number option

Load Case Editor:

  • Added import of a properly formatted Excel .xlsx file into the Static Analysis – Load Case Editor. The software also provides an example template file, LCE_Template.xltx, in the C:\\ProgramData\Intergraph CAS\CAESAR II\11.00\System\templates folder.
  • Added export of an Excel .xlsx file from the Static Analysis – Load Case Editor.
  • Added an Exclude option that allows you to easily remove a selected load case from the static analysis.
  • Updated the Static Analysis – Load Case Editor for the DNV 2017 piping code, including a new limit state (LMST) stress type for combined load cases, and a new Limit State Load Type field for non-combined load cases and non-LMST combined loads. 
  • For ASME NC-3658.3 flanged joint calculations, changed the hydrotest (HYD) load cases to use the same allowable as the occasional (OCC) load cases. 

Piping, Equipment, and Environmental Codes:

  • Added support for ASCE 7-2016 wind and seismic loads.
  • Added support for the China GB 50009-2012 wind code.
  • Added support for the ISO 14692 2017 piping code.
  • Added support for the DNV 2017 (DNVGL-ST-F101) piping code, including a new DNV/Offshore tab for Special Execution Parameters.
  • Updated the CODETI code to the November 2016 edition, and corrected CODETI code stress equations in the Quick Reference Guide.
  • Updated the KHK Seismic Design Guideline for the High-Pressure Gas Facilities to the 2012 edition.
  • Updated the ASME B31.1 code to the July 2018 edition.
  • Updated the BS EN 13480 code to the June 2017 edition.
  • Updated the Errors and Warnings grid to perform more like Microsoft Excel. The grid supports selection and copy of grid rows between the grid and Excel.
  • For the Seismic Wizard, changed the default value for the ASCE 7 Response Factor R from 12 to 3.5 to comply with ASME B31.
  • Added support for displaying all component stress values (hoop, allowable, SIF) in reports instead of only the highest component stress.

Material and Content:

  • Updated the Material Database Editor grid to support copy, cut, paste, and delete of cells and rows within the grid and between the grid and Excel.
  • Updated the hanger table for LISEGA.

Configuration:

  • Updated B31.4 and B31.8 codes to function similarly for non-default configuration settings and combination load cases.

Equipment:

  • Expanded the redesigned Equipment Manager to include API 617, API 560, API 661, NEMA SM23, and HEI Standard equipment modules into the single Equipment Manager window. (API 610 equipment was moved into the Equipment Manager in the previous release.) Changes include updates to calculations and updates to reports to meet Equipment Manager standards.
  • Added several usability improvements. Node Number is now optional. Most recently used files are now available. Status and warnings for the equipment input display before analysis and in the status pane and in the output report after analysis completes.

Analysis:

  • For static analysis, clarified the usage of the wind load reduction factor for ASCE 7. You must explicitly apply this factor to the wind load component in a wind load case. 
  • For dynamic analysis, corrected the determination of the pressure stiffening effect on bends by excluding hydro pressure.

User Interface:

  • Added shortcut keys that are used consistently throughout the software.
  • Improved the File tab options on the main window ribbon, including improved existing options, and new folder and help access.
  • Removed the secondary menu from the main window. All commands are on the main window ribbon.
  • Added a new Layout menu to the main window ribbon. The menu provides theme, language, and icon size options and allows you to reset to the default layout.
  • Changed the default look of the software to a new light gray Light theme. The existing dark gray Dark theme is available on the Layout menu.
  • Changed some graphics defaults to better match the most commonly-used settings. New defaults include: Default Operator (Select), Hide Overlapping Text (on), Text Options (12 pt. by default), and Bottom and Top background colors (white).
  • Updated the File > About window to improve usability and appearance. Also updated the Help and About icons to provide a look consistent with other interface improvements.
  • Updated the Help tab to eliminate unnecessary commands, better organize the remaining commands, and provide a new help search function. 

Isometrics:

  • Added the option to create .pdf files when you create .dwg files using Create Isometric Drawings. The software also saves .dwg drawing files and .pdf files in the same folder as the piping model.
  • Updated Generate Stress Isometrics to Personal ISOGEN 2016 (10.0.0.1) and to I-Configure 2016 (06.00.00.11).
  • Improved the creation of isometric drawings for models containing dummy legs.
  • Improved usability of stress isometric annotations. When you select a Restraint/Hanger Types or SIF/Fitting Data input feature, the software also selects the corresponding Node Numbers feature.

Underground Pipe Modeler:

  • Updated the Underground Pipe Modeler grid to support copy and paste of rows within the grid and between the grid and Excel.

Output Processor:

  • Added access to the Data Export Wizard from the Static Output Processor. 
  • Added a Maximize/Restore button to report windows for static reports. The software also saves the most recent window size and uses it when you open the next report window.
  • Changed standard reports to more consistently report component stresses. Created a standard Stresses report, a new Stresses (Multiple Code/Allow.) report for transportation and offshore codes. Changed the Stresses Extended report to the Stresses Extended (Legacy) report. Removed the previous Stress and Code Compliance reports. Renamed the Code Compliance Extended report to Code Compliance.

Configuration:

  • Updated B31.4 and B31.8 codes to function similarly for non-default configuration settings and combination load cases.

Material and Content:

  • Updated the Material Database Editor grid to support copy, cut, paste, and delete of cells and rows within the grid and between the grid and Excel.
  • Updated the hanger table for LISEGA.

External Interfaces:

  • Improved Import PCF to allow you to import a large number of files.
  • Added an interface for BOSfluids file import, using a dialog box similar to the other hydraulic module interfaces. Also added an option to directly open Dynamic Analysis after import completes.
  • Updated the neutral file format so that line numbers, line color, line visibility, and bend overlay thickness now import and export.
  • Improved the Data Export Wizard to allow multiple output report exports in one session. Improved defaults of the Input and Output Files window and changed the default output file format to .accdb (Microsoft Office 2007 and later Access database) to improve usability.

Documentation/Help:

  • Converted help to a new help viewer with an improved interface and search, and changed the format of units to eliminate display issues.
  • Updated thermal coefficient of expansion topics to specify the length and temperature units of the model.
  • Added more details and equations to the CAESAR II Determines option of Allowable Stress Indicator for finding the pipe restrained/unrestrained status in the B31.4 code.
  • Clarified usage of the Free Measure option of Distance. The option should only be used in 2D views.
  • Added a shortcut key overview to the Quick Reference Guide.
  • Added information on editing ASCII text files.
  • Clarified descriptions of numeric calculations in delta and length fields of Classic Piping Input.
  • Added descriptions for Multiple Load Case Hanger Design Options in the Hangers auxiliary panel, the Hanger Design Control Data dialog box of Classic Piping Input, and the Technical Discussions section.
  • Added a note to Type for SIFs & Tees that describes the importance of properly defining tees to avoid overly conservative SIF values.

Learn the changes in the different versions of Caesar II software:

Caesar II Version 12 vs Caesar II Version 11
Major features of CAESAR II-2019, Version 11.00
Added Features of CAESAR II 2018, Version 10.00
What’s New in CAESAR II, 2016 (Version 8.0)
Practical changes in Caesar II version 7.0 (2014) with respect to its earlier version.

Procedure for Converting a Higher version Caesar II file into its Lower version

Many a time during interfacing with other EPC organizations or vendors, Caesar II file transfer becomes a necessity to reduce re-modeling time. And most of the time it happens that the Caesar II versions do not match. The caesar files with the lower version (i.e., version 7.0) easily open in their higher version. But if the file received is of a higher version (i.e., version 8.0) then it’s difficult to open in the lower version. For opening such files into the lower version there is a trick. One has to follow the neutral file methodology for such activities. In this article, the procedure for opening a caesar II file version 8.0 into caesar II version 7.0 will be explained.

However, it’s not suggested to use a lower version of the software for a higher version file as due to changes in codes the results of both versions will be different. So the same situation must be handled with utmost care.

Neutral file Conversion

Ask the neutral file of the higher version from other contractor r vendors. The procedure for neutral file conversion is explained below in Fig. 1 and 2.

Procedure for making Neutral file from caesar II file
Fig. 1: Procedure for making Neutral file from caesar II file

The Caesar II neutral file will be created in the same folder where the original file is stored. Refer to Fig. 2 to know the generated Neutral file.

Neutral file in the same path of original file.
Fig. 2: Neutral file in the same path as the original file.

Neutral file to Caesar II file conversion

Once you possess the Neutral file of the higher version and saved it in some known path, Open the Caesar II lower version (7.0). In a similar way again go to Interfaces—-Caesar II neutral file—-Convert Neutral file to caesar II input file. And follow the steps mentioned in Fig. 3

Generation of Caesar II file from Neutral file.
Fig. 3: Generation of Caesar II file from Neutral file.

Now Caesar II file is ready to open in your version of the software. Note that the load cases you have to prepare them again.

The Caesar II version 2016 (8.0) file I could able to open in Version 2014 and Version 2013 R1 but it does not open on Version 2011 R1. It showed an error and the conversion could not succeed.

For some years, It was not possible to open upper-version C2 files into the lower versions. But again the feature is active in recent versions. Mostly after the completion of the Caesar II software takeover process by Hexagon, wherever a new version of Caesar II software is released by Hexagon their Caesar II files can be opened in the lower versions by following the above-mentioned method.

However, for opening a caesar file of version 12.0 into its lower version 11.0, neutral file conversion is not required. The caesar ii files of version 12 automatically open in caesar ii version 11 (2019).